Skip to Content

Rule

Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies

This document is a correction of a document that was published on 01/10/2020. View Uncorrected Document

Document Details

Information about this document as published in the Federal Register.

Document Statistics
Document page views are updated periodically throughout the day and are cumulative counts for this document including its time on Public Inspection. Counts are subject to sampling, reprocessing and revision (up or down) throughout the day.
Enhanced Content

Relevant information about this document from Regulations.gov provides additional context. This information is not part of the official Federal Register document.

Published Document

This document has been published in the Federal Register. Use the PDF linked in the document sidebar for the official electronic format.

Start Preamble

Correction

In rule document 2019-2635 beginning on page 1447 in the issue of Friday, January 10, 2020, make the following correction:

[Corrected]

On page 1503, in § 430.32(z)(3) the table should appear as follows:

Battery charger product classRated output powerMinimum efficiency
10a (VFD UPSs)0 W < P rated ≤ 300 W−1.20E-06 * P2 rated + 7.17E-04 * P rated + 0.862.
300 W < P rated ≤ 700 W−7.85E-08 * P2 rated + 1.01E-04 * P rated + 0.946.
P rated > 700 W−7.23E-09 * P2 rated + 7.52E-06 * P rated + 0.977.
10b (VI UPSs)0 W < P rated ≤ 300 W−1.20E-06 * P2 rated + 7.19E-04 * P rated + 0.863.
300 W < P rated ≤ 700 W−7.67E-08 * P2 rated + 1.05E-04 * P rated + 0.947.
P rated > 700 W−4.62E-09 * P2 rated + 8.54E-06 * P rated + 0.979.
10c (VFI UPSs)0 W < P rated ≤ 300 W−3.13E-06 * P2 rated + 1.96E-03 * P rated + 0.543.
300 W < P rated ≤ 700 W−2.60E-07 * P2 rated + 3.65E-04 * P rated + 0.764.
P rated > 700 W−1.70E-08 * P2 rated + 3.85E-05 * P rated + 0.876.